Performance of Single Phase PV Integrated DSTATCOM Operating 1n Polluted Utility Condition
IR@CEERI: CSIR-Central Electronics Engineering Research Institute, Pilani
View Archive InfoField | Value | |
Title |
Performance of Single Phase PV Integrated DSTATCOM Operating 1n Polluted Utility Condition
|
|
Creator |
Verma, BK
Dcvassy, S Ram , SK Abhishcek, Anand Dhakar, AK |
|
Subject |
Industrial Electronics
|
|
Description |
Abslm cl- In this paper, a control technique based on cas1:aded second order-generalized integrator (CSOGI) is present ed for the control of s ing ltf phase pho t ovoltaic integrated distribution static compensator -tt'V-DSTAT COIVI ). The system rnmpensatcs for reactive power and harmonics in the load current along with injecting power from PV array. Two SOG I blocks arc used to ext ral'l the fundamental component of grid voltage and load ntrrent whid1 is then used in rnntrol of PV-DSTATCOIVI. Due to the cascaded structure, CSOGI can hetter filter the third and firth harmonic voltage present in t he gri d and can extract the fundam ental component. Max imum power point tn Kkin g (MPPT) algorithm is used to get the reference voltage for ck-link vol tage control. Systc lll pcrf'o rllla nc e is evaluated by silllulating it in IVIATLAB/Simulink environment under dynamic conditions like irrndiation and load change.
|
|
Date |
2017-12-22
|
|
Type |
Conference or Workshop Item
PeerReviewed |
|
Format |
application/pdf
|
|
Identifier |
http://ceeri.csircentral.net/371/1/54-2017.pdf
Verma, BK and Dcvassy, S and Ram , SK and Abhishcek, Anand and Dhakar, AK (2017) Performance of Single Phase PV Integrated DSTATCOM Operating 1n Polluted Utility Condition. In: P E S TS E 2018, Jan. 18-20, 2018, Banguluru. (Submitted) |
|
Relation |
http://ceeri.csircentral.net/371/
|
|